Pole Mounted Overhead Voltage Transformer Single Phase For America, Canada Model Number: D11
| Model Series | D11 |
| Rated Voltage | 2.5~34.5kV |
| Standard | IEEE C57.12.20 |
| Warranty | Two years |
| Application | Outdoor/Indoor |
1. Primary Electrical Distribution & Grid Layouts
-
Standalone Single-Phase Supply: The transformer can be used independently to step down medium-voltage utility lines (ranging from 2.5kV up to 34.5kV) down to low-voltage service levels (such as 120/240V, 240/480V, or 600V) to directly power local single-phase loads.
-
Three-Phase Bank Configurations: For commercial or industrial settings requiring three-phase power, multiple individual single-phase units (typically a bank of three) can be cluster-mounted together on a single pole or structurally interconnected to supply a three-phase distribution network.
2. Regional and Sector Deployments
-
Rural and Remote Power Distribution: Because single-phase overhead lines are highly cost-effective over long distances, these pole-mounted transformers are ideal for extending the electrical grid to rural areas, isolated farmlands, remote regions, and scattered village communities.
-
Residential & Neighborhood Grid Supply: They provide the final step-down voltage required for clean, reliable power routing for daily residential use, domestic appliances, and local street or public lighting infrastructure.
-
Agricultural Production: Powering standard farm infrastructure, including irrigation pumping systems, livestock housing ventilation, sorting machinery, and workshop tools.
-
Light Industrial and Commercial Facilities: Suitable for isolated workshop facilities, small-scale industrial plants, or roadside commercial operations that do not require massive substations but need independent grid tie-ins.
3. Modernization & Infrastructure Upgrades
-
Urban Grid Overhauls & Energy-Saving Projects: Built to modern efficiency benchmarks (such as DOE 2016 and NEMA TP1 standards) with specialized CRGO or Amorphous cores, these transformers are commonly utilized in urban power grid reconstruction and infrastructure upgrades aiming to drastically reduce idle core losses and line resistance.
-
Railway Infrastructure Powering: Integrated into the peripheral networks of rail systems to reliably feed auxiliary equipment, signaling systems, stations, and maintenance yards along transit routes.
4. Environmental & Installation Versatility
-
Flexible Overhead Mounting: Engineered to be bolted directly to wooden, steel, or concrete utility poles via standard support brackets, saving valuable ground real estate in congested or geographically challenging terrains.
-
Heavy-Duty Weather Resilience: Designed to IEEE C57 standards for robust enclosure integrity, making them highly suited for both extreme outdoor and sheltered indoor operations across wide temperature fluctuations (-25°C to +40°C).
General

Product Standards
Main Features
Quality Assurance

| Table of Liquid Single phase pole mounted transformer (<150kV BIL) Temp rise 65℃ | ||||||||
| kVA | Primary voltage | Secondary voltage | A mm | B mm | C mm | Weight (kG) | Efficiency % | |
| DOE2016 | NEMA TP1 | |||||||
| 10 | 4160 7200 7620 12470 13200 13800 24940 19920 | 120/240 240/ 480 277 346 600 | 530 | 600 | 1060 | 160 | 98.70% | 98.40% |
| 15 | 530 | 600 | 1060 | 180 | 98.82% | 98.60% | ||
| 25 | 580 | 660 | 1080 | 230 | 98.95% | 98.70% | ||
| 37.5 | 610 | 690 | 1090 | 290 | 99.05% | 98.80% | ||
| 50 | 650 | 700 | 1100 | 340 | 99.11% | 98.90% | ||
| 75 | 680 | 750 | 1250 | 450 | 99.19% | 99.00% | ||
| 100 | 730 | 800 | 1250 | 500 | 99.25% | 99.00% | ||
| 167 | 900 | 850 | 1300 | 780 | 99.33% | 99.10% | ||
| 250 | 1200 | 900 | 1450 | 1100 | 99.39% | 99.20% | ||
| 333 | 1350 | 1200 | 1500 | 1300 | 99.43% | 99.20% | ||
Production Workshop